Moxa iologik E1214
Hinnat näkyvät kirjautuneille jälleenmyyjille.
OBSERON LPR TCP/IP I/O Moduli 6 In/6 Out
Kuvaus
| ioLogik E1214:n tekniset tiedot | |
| • Inputs and Outputs | |
| Digital Inputs | 6 channels |
| Relay Outputs | 6 channels |
| Isolation | 3k VDC or 2k Vrms |
| • Digital Input | |
| Sensor Type | Wet Contact (NPN or PNP), Dry Contact |
| I/O Mode | DI or Event Counter |
| Dry Contact | • On: short to GND • Off: open |
| Wet Contact (DI to COM) | • On: 10 to 30 VDC • Off: 0 to 3 VDC |
| Common Type | 6 points per COM |
| Counter Frequency | 250 Hz |
| Digital Filtering Time Interval | Software Configurable |
| • Relay Output | |
| Type | Form A (N.O.) power relay |
| Contact Current Rating | Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC |
| Breakdown Voltage | 500 VAC |
| Relay On/Off Time | 1500 ms (max.) |
| Initial Insulation Resistance | 1000 M ohms (min.) @ 500 VDC |
| Mechanical Endurance | 5,000,000 operations |
| Electrical Endurance | 100,000 operations @ 5 A resistive load |
| Contact Resistance | 100 m ohms (max.) |
| Pulse Output | 0.3 Hz at rated load |
| Note | Ambient humidity must be non-condensing and remain between 5 and 95%. The relays of the ioLogik E1214 may malfunction when operating in high condensation environments below 0° Celsius. |
| • Power Requirements | |
| Power Consumption | 188 mA @ 24 VDC |
| • MTBF (mean time between failures) | |
| Time | 808,744 hrs |
| Database | Telcordia (Bellcore) |
| Common Specifications | |
| • LAN | |
| Ethernet | 2 switched 10/100 Mbps RJ45 ports |
| Protection | 1.5 kV magnetic isolation |
| Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, HTTP |
| • Power Requirements | |
| Power Input | 24 VDC nominal, 12 to 36 VDC |
| • Physical Characteristics | |
| Wiring | I/O cable max. 14 AWG |
| Dimensions | 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
| Weight | Under 200 g |
| Mounting | DIN rail or wall |
| • Environmental Limits | |
| Operating Temperature | Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| Altitude | Up to 2000 m |
| Note | Please contact Moxa if you require products guaranteed to function properly at higher altitudes. |
| • Standards and Certifications | |
| Safety | UL 508 |
| EMI | EN 55022; EN 61000-3-2; EN 61000-3-3; FCC Part 15, Subpart B, Class A |
| EMS | EN 55024, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11 |
| Shock | IEC 60068-2-27 |
| Freefall | IEC 60068-2-32 |
| Vibration | IEC 60068-2-6 |
| Green Product | RoHS, CRoHS, WEEE |
| Hazardous Location | UL/cUL Class I Diision 2, ATEX Zone 2 |
| • Warranty | |
| Warranty Period | 5 years (excluding ioLogik E1214) |
| Details | See www.moxa.com/warranty |
| Note | Because of the limited lifetime of power relays, products that use this component are covered by a 2-year warranty. |